Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

01/30/2009

Applicant:

BROADWAY-CRAYCROFT LLC

Description:

Full Inspection conducted: 1/21/09 Report Delivered: 03/11/09 Re-inspection: 03/25/09 (or after) If you have any questions please call, 791-4502 I have received a copy of this report: __________________ Business Representative: Avery Harper Inspector: __________________, Captain: _____________ David Greenleaf, MA 23

Outstanding Inspections

Case Number: T09FR00418
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date Description Inspector Results Comments
01/21/2009 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
01/21/2009 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.4.1 - Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363.
01/21/2009 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
01/21/2009 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.4.3 - Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors, under doors or floor coverings, or be subject to environmental or physical damage.
01/21/2009 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
01/21/2009 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1001.2 - Minimum requirements. It shall be unlawful to alter a building or structure in a manner that will reduce the number of exits or the capacity of the means of egress to less than required by this code.
01/21/2009 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building.
01/21/2009 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting
01/21/2009 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1008.1.8 - Door operations. ...egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Replace key-turn deadbolt with thumb-turn on egress side of rear door.
01/21/2009 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Exceptions: 2. Main exterior exit doors or gates that are obviously and clearly identifiable as exits need not have exit signs where approved by the fire code official.
01/21/2009 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs
03/04/2009 VIOL - FIRE SERVICE FEATURES DGREENLE Correction Required TFC 504.2 - Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. _____ Open blocked exits or obtain approval and eliminate them in an approved manner.
03/10/2009 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required TFC 903.2.10 - Windowless stories in all occupancies. An automatic sprinkler system shall be installed in the locations set forth in Sections 903.2.10.1 through 903.2.10.1.3. (1. Deleted) 2. Openings entirely above the adjoining ground level totaling at least 20 square feet (1.86 m2) in each 50 linear feet, or fraction thereof, of exterior wall in the story on at least one side. TFC 903.2.10.1.1 Opening dimensions and access. Openings shall have a minimum dimension of not less than 30 inches. Such openings shall be accessible to the fire department from the exterior and shall not be obstructed in a manner that fire fighting or rescue cannot be accomplished from the exterior. TFC 903.2.10.1.2 Openings on one side only. Where openings in a story are provided on only one side and the oppositewall of such story is more than 75 feet from such openings, the story shall be equipped throughout with an approved automatic sprinkler system or openings as specified above shall be provided on at least two sides of the story. _____ Doors in rear of building shall be returned to service. The Fire Marshall will entertain an appeal to remove from service the West doors and door from shop area.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00418
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
03/10/2009 INSP - FULL DGREENLE Approved -- PrFF Joey Crandle assisting, -- Teresa Ryberg, Property Manager - PICOR, 546-2719
12/29/2009 INSP - REINSPECTION dgreenl1 Approved appeal granted RI - COMPLETE