Case: T09FR00418

Parcel: 12803078A


Addresses:

5626 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR00418

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/21/2009 VIOL - MEANS OF EGRESS Correction Required TFC 1001.2 - Minimum requirements. It shall be unlawful to alter a building or structure in a manner that will reduce the number of exits or the capacity of the means of egress to less than required by this code.
01/21/2009 VIOL - MEANS OF EGRESS Correction Required TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.

_____ Provide emergency lighting that is activated by loss of power to building.
01/21/2009 VIOL - MEANS OF EGRESS Correction Required TFC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate…
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator.

_____ Repair or replace batteries in emergency lighting
01/21/2009 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8 - Door operations. ...egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____ Replace key-turn deadbolt with thumb-turn on egress side of rear door.
01/21/2009 VIOL - MEANS OF EGRESS Correction Required TFC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Exceptions:
2. Main exterior exit doors or gates that are obviously and clearly identifiable as exits need not have exit signs where approved by the fire code official.
01/21/2009 VIOL - MEANS OF EGRESS Correction Required TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated.

_____ Repair/replace exit signs