Food city full fire inspection.

Outstanding Inspections

Case Number: T09FR00089
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
01/08/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
01/08/2009 VIOL - FIRE RESIST.RATED CONST JLOYA Violation TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles
01/08/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ***A K class extinguisher shall be installed according to this code.
01/08/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code.
01/08/2009 VIOL - MEANS OF EGRESS JLOYA Violation Security bolt on rear door: To ensure that there is no confusion on the required exiting from the building the following must be completed: 1. A sign stating "NOT AN EXIT" affixed to the interior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background. 2. A sign stating "THIS DOOR BLOCKED" affixed to the exterior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00089
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
01/08/2009 INSP - FULL JLOYA Approved Correct the following fire code violations, thank you for your cooperation.
01/22/2009 INSP - REINSPECTION JLOYA Approved All violations abated.