Case: T09FR00089
Case Details
Entered Date:
01/08/2009
Applicant:
PVP7 LLC
Description:
Food city full fire inspection.
Outstanding Inspections
Case Number: T09FR00089
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. |
01/08/2009 | VIOL - FIRE RESIST.RATED CONST | JLOYA | Violation | TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles |
01/08/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ***A K class extinguisher shall be installed according to this code. |
01/08/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code. |
01/08/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | Security bolt on rear door: To ensure that there is no confusion on the required exiting from the building the following must be completed: 1. A sign stating "NOT AN EXIT" affixed to the interior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background. 2. A sign stating "THIS DOOR BLOCKED" affixed to the exterior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00089
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2009 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations, thank you for your cooperation. |
01/22/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |