Case: T09FR00089

Parcel: 119215910


Addresses:

1740 W AJO WY


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR00089

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
01/08/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
***A K class extinguisher shall be installed according to this code.
01/08/2009 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

_____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code.