Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/08/2009

Applicant:

SAN XAVIER PLAZA LLC

Description:

Family dollar full fire inspection

Outstanding Inspections

Case Number: T09FR00066
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
01/08/2009 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings.
01/08/2009 VIOL - FIRE RESIST.RATED CONST JLOYA Violation TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles.
01/08/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting
01/08/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.2 Door swing. Egress doors shall be side-hinged swinging. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy.
01/08/2009 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way.
01/08/2009 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00066
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
01/08/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found 1-7-09. Thank you for your cooperation.
01/22/2009 INSP - REINSPECTION JLOYA Approved All violations abated.