Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T09FR00066

Parcel: 11941176H


Addresses:

1785 W AJO WY


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR00066

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
01/08/2009 VIOL - MEANS OF EGRESS Violation 1008.1.2 Door swing. Egress doors shall be side-hinged swinging.
Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy.
01/08/2009 VIOL - MEANS OF EGRESS Violation TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated.

_____ Repair/replace exit signs
01/08/2009 VIOL - MEANS OF EGRESS Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate…
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator.

_____ Repair or replace batteries in emergency lighting
01/08/2009 VIOL - MEANS OF EGRESS Violation TFC 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.

_____ Clear exit path, and maintain it this way.