Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

12/30/2008

Applicant:

GORDON HERMAN D & JEAN L FAMILY TR

Description:

SPRINKLER INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04825
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/30/2008 INSP - FULL EDESCHAI Approved DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED DURING THE SCHEDULED REMODEL. 1) GUAGES AT THE SPRINKLER RISER ARE DUE FOR THE 5 YEAR CALIBRATION OR TO BE CHANGED OUT 2) ALL LOADED SPRINKLER HEADS AND THOSE WITH BENT DEFLECTORS SHALL BE CHANGED OUT. 3) A SPRINKLER HEAD NEEDS TO BE ADDED TO A CORNER BOOTH