Case: T08FR04809
Case Details
Entered Date:
12/26/2008
Applicant:
PARK MALL LLC
Description:
Applebees #E-1 (aka 3005) Full inspection conducted 10/8/08 w/PRFF held pending recipt of hood system report Hood report CO T08FR04803
Outstanding Inspections
Case Number: T08FR04809
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/26/2008 | VIOL - ADMINISTRATION | DGREENLE | Correction Required | TFC 107.2.2 - Reinspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made so as to achieve compliance with this code. The work or installation shall then be resubmitted to the fire code official for inspection and testing. _____ perform all necessary repairs to hood extinguishing system as noted in inspection report from Centurion Fire Protection dated 11/12/08, per CO T08FR04803 |
12/26/2008 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Correction Required | TFC 315.2.1 - Ceiling clearance. Storage shall be maintained a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. _____ walk in freezer |
12/26/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.4.3 - Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors, under doors or floor coverings, or be subject to environmental or physical damage. TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Power cord through ceiling. |
12/26/2008 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Correction Required | 904.11.6.1 Ventilation system. The ventilation system in connection with hoods shall be operated at the re-quired rate of air movement, and classified grease filters shall be in place when equipment under a kitchen grease hood is used. _____ Eliminate spaces between grease filters. |
12/26/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Correction Required | TFC 1027.5 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: _____ Test emegency lighting and repair/replace where necessary. |
12/26/2008 | VIOL - COMPRESSED GASES | DGREENLE | Correction Required | TFC 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. _____ Secure gas cylinder in an approved manner. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04809
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/26/2008 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy: ON FILE - occ type: A-3 - occ load: 193 Extinguishers tagged 4/08 Sprinkler systen tagged 6/08 (Hood tagged 4/08, due for service, Mgr says they plan to replace) Pull station for hood system blocked, cleared prior to leaving |
01/20/2009 | INSP - REINSPECTION | DGREENLE | Approved | All violations corrected - PASSED |