Description:

La Bella China restaurant full fire inspection

Outstanding Inspections

Case Number: T08FR04766
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
12/19/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
12/19/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited
12/19/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. _____ Remove extension cord and/or replace with approved permanent electrical power source.
12/19/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ***K class extinguisher shall be inspected according to this code.
12/19/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. ___ Provide record stating such cleanouts.
12/19/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04766
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/19/2008 INSP - FULL JLOYA Approved Correct the following fire code violations found 12-18-08. For your cooperation, thank you.
01/21/2009 INSP - REINSPECTION JLOYA Approved All violations abated.