Case: T08FR04766

Parcel: 13710510A


Addresses:

5680 S 12TH AV


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR04766

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
12/19/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment
12/19/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
___ Provide record stating such cleanouts.
12/19/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
***K class extinguisher shall be inspected according to this code.