Case: T08FR04763
Case Details
Entered Date:
12/18/2008
Applicant:
TUCSON PLACE PARTNERS LLC
Description:
Full Fire Prevention Inspection. Sam Alboy 292-2600
Outstanding Inspections
Case Number: T08FR04763
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. ____1.Remove all storage from obstructing the electrical service equipment located in the kitchen by the back door. |
12/18/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____1.The exit sign located by the East exit door shall be fully illuminated. |
12/18/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.Test all emergency lighting units located in the building and repair or replace all defective units. |
12/18/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by the following method. Secure containers, cylinders and tanks to a fixed object with one or more restraints. _____1.Properly secure the CO2 cylinder located in the kitchen by the back door. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04763
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2008 | INSP - FULL | JBURGE | Approved | Please correct all noted Tucson Fire Code violations. |