Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/18/2008

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full Fire Prevention Inspection. Sam Alboy 292-2600

Outstanding Inspections

Case Number: T08FR04763
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
12/18/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. ____1.Remove all storage from obstructing the electrical service equipment located in the kitchen by the back door.
12/18/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____1.The exit sign located by the East exit door shall be fully illuminated.
12/18/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.Test all emergency lighting units located in the building and repair or replace all defective units.
12/18/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by the following method. Secure containers, cylinders and tanks to a fixed object with one or more restraints. _____1.Properly secure the CO2 cylinder located in the kitchen by the back door. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04763
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/18/2008 INSP - FULL JBURGE Approved Please correct all noted Tucson Fire Code violations.