Description:

SPRINKLER INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04730
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/15/2008 INSP - FULL EDESCHAI Approved DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE CORRECTION MANIFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE 1) THE MAIN CONRTOL VALVE IS SHALL BE SECURED WITH A LOCK AND CHAIN 2) THE SPRINKLER RISER IS DUE FOR THE 5 YEAR INTERNAL VALVE INSPECTION 3) THE WATER MOTOR GONG FAILED TO WORK AND SHALL BE REPAIRED 4) SUITE # 202 SHALL HAVE SPRINKLER PROTECTION ADDED TO THE EAST CENTER BREAK ROOM