Case: T08FR04730

Parcel: 11207271A

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/28/2009 INSP - FULL Approved APPROVED BY FIELD INSPECTION AND CONTRACTORS REPORTS
06/16/2009 INSP - FULL Correction Required * NOTE *
ALL ITEMS HAVE BEEN CORRECTED WITH THE EXCEPTION OF
# 4. THE WALL CAN BE REMOVED OR CAN BE CUT DOWN TO 24 INCHES FROM THE CEILING. PLEASE CALL FOR A REINSPECTION. THANK YOU.
04/10/2009 INSP - FULL Correction Required PRECITATION SENT 4-8-09
02/10/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 12-15-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 2761 N. COUNTRY CLUB. IF CORRECTED, HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
12/15/2008 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE CORRECTION MANIFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE

1) THE MAIN CONRTOL VALVE IS SHALL BE SECURED WITH A LOCK AND CHAIN

2) THE SPRINKLER RISER IS DUE FOR THE 5 YEAR INTERNAL VALVE INSPECTION

3) THE WATER MOTOR GONG FAILED TO WORK AND SHALL BE REPAIRED

4) SUITE # 202 SHALL HAVE SPRINKLER PROTECTION ADDED TO THE EAST CENTER BREAK ROOM