Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR04730
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2009 | INSP - FULL | Approved | APPROVED BY FIELD INSPECTION AND CONTRACTORS REPORTS | |
| 06/16/2009 | INSP - FULL | Correction Required | * NOTE * ALL ITEMS HAVE BEEN CORRECTED WITH THE EXCEPTION OF # 4. THE WALL CAN BE REMOVED OR CAN BE CUT DOWN TO 24 INCHES FROM THE CEILING. PLEASE CALL FOR A REINSPECTION. THANK YOU. |
|
| 04/10/2009 | INSP - FULL | Correction Required | PRECITATION SENT 4-8-09 | |
| 02/10/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 12-15-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 2761 N. COUNTRY CLUB. IF CORRECTED, HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
| 12/15/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE CORRECTION MANIFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE 1) THE MAIN CONRTOL VALVE IS SHALL BE SECURED WITH A LOCK AND CHAIN 2) THE SPRINKLER RISER IS DUE FOR THE 5 YEAR INTERNAL VALVE INSPECTION 3) THE WATER MOTOR GONG FAILED TO WORK AND SHALL BE REPAIRED 4) SUITE # 202 SHALL HAVE SPRINKLER PROTECTION ADDED TO THE EAST CENTER BREAK ROOM |