Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/04/2008

Applicant:

ROSE DELA DMA FLP

Description:

El tortillero (la unica) full fire inspection

Outstanding Inspections

Case Number: T08FR04564
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 14
End Date Description Inspector Results Comments
12/04/2008 VIOL - ADMINISTRATION JLOYA Violation 105.6.11 Cutting and welding. An operational permit is required to conduct cutting or welding operations within the jurisdiction. ___WELDING IS NOT PERMITED ANY WHERE INSIDE THE BUILDING WITH OUT A PERMIT
12/04/2008 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. ____ Maintain area around water heaters clear of combustibles.
12/04/2008 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation TFC 304.2 - Storage. Storage of combustible rubbish shall not produce conditions that will create a nuisance or a hazard to the public health, safety or welfare. ___ Maintain storage room by main office clear of excesive combustible materials.
12/04/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear and maintain clear area around electrical panels.
12/04/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. __ Several multiplug adapters were found troughout the building, remove/replace with approved power strip.
12/04/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. ___ Power strips shall not be connected to extension cords or another power strip.
12/04/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. _____ Remove extension cord and/or replace with approved permanent electrical power source.
12/04/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ____Cover al exposed wiring .
12/04/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ***A K class extinguisher shall be installed according to this code. ___ Provide such extinguisher by "corn chip" making room. Extiguisher shall be properly mounted, unobstructed and unobscured.
12/04/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. ___Provide cleaning records for all extractors in property.
12/04/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. ___The hood exhaust and extinguishing systems shall be inspected and tagged.
12/04/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.5 Fusible link and sprinkler head replacement. Fusible links and automatic sprinkler heads shall be replaced at least annually, and other protection devices shall be serviced or replaced in accordance with the manufacturer's instructions.
12/04/2008 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs
12/04/2008 VIOL - COMPRESSED GASES JLOYA Violation 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04564
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/04/2008 INSP - FULL JLOYA Approved Correct the following fire code violations found 12-3-08.
12/22/2008 INSP - REINSPECTION JLOYA Approved All violations abated.