Description:

99 cent and less full fire inspection

Outstanding Inspections

Case Number: T08FR04551
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/03/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. _____ Remove extension cord and/or replace with approved permanent electrical power source
12/03/2008 VIOL - MEANS OF EGRESS JLOYA Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting
12/03/2008 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate.
12/03/2008 VIOL - MEANS OF EGRESS JLOYA Violation 1023.6 Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way. ___ Relocate rear exit to original location.
12/03/2008 VIOL - MEANS OF EGRESS JLOYA Violation 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgement and against access by unauthorized personnel in accordance with Sections 3003.5.1 through 3003.5.3.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04551
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/03/2008 INSP - FULL JLOYA Approved Correct the following code violations found 12-2-08.
12/04/2008 INSP - REINSPECTION JLOYA Approved All violations abated