Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/01/2008

Applicant:

HENRY CMT DELB FLP

Description:

El potrero full fire inspection

Outstanding Inspections

Case Number: T08FR04510
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
12/01/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
12/01/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove extension cord and/or replace with approved permanent electrical power source.
12/01/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
12/01/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. ___ Replace hood system grease filters
12/01/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. ___ Provide records of last exhaust sytem clean up.
12/01/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04510
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/01/2008 INSP - FULL JLOYA Approved Correct the following fire code violations found 11-28-08 during fire safety inspection.
01/12/2009 INSP - REINSPECTION JLOYA Approved all violations abated