Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T08FR04510
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
|
12/01/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove extension cord and/or replace with approved permanent electrical power source. |
|
12/01/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |