Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

12/01/2008

Applicant:

R J & J LLC

Description:

Bojangle's exiting complaint inspection.

Outstanding Inspections

Case Number: T08FR04503
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/01/2008 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1 Doors. Means of egress doors shall be readily distinguishable from the adjacent construction and finishes such that the doors are easily recognizable as doors
12/01/2008 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.
12/01/2008 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way.
12/01/2008 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building.
12/01/2008 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04503
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/01/2008 INSP - LIFE SAFETY JLOYA Approved Life safety inspection conducted 11-28-08. Correct the following violations.
12/11/2008 INSP - REINSPECTION JLOYA Approved All violations abated.