Case: T08FR04452
Case Details
Entered Date:
11/26/2008
Applicant:
VALENCIA COMMERCE CENTER LLC
Description:
Orthodontic proffessionals full fire inspection for recomendation into self inspection program
Outstanding Inspections
Case Number: T08FR04452
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2008 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. |
11/26/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04452
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2008 | INSP - FULL | JLOYA | Approved | Correct the following code violations found 11-25-08 durin annual fire safety fire inspection. |
12/04/2008 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |