Case: T08FR04451
Case Details
Entered Date:
11/26/2008
Applicant:
VALENCIA COMMERCE CENTER LLC
Description:
People's Choice Video full fire inspection
Outstanding Inspections
Case Number: T08FR04451
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2008 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. |
11/26/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
11/26/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. |
11/26/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. |
11/26/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |
11/26/2008 | VIOL - FIRE RESIST.RATED CONST | JLOYA | Violation | TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles. |
11/26/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. |
11/26/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | TFC 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way. |
11/26/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04451
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2008 | INSP - FULL | JLOYA | Approved | Correct the following violations found 11-25-08 during annual fire and safety inspection. |
01/12/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |