Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/26/2008

Applicant:

VALENCIA COMMERCE CENTER LLC

Description:

Lesko Optical fire inspection for recomendation into self inspection program

Outstanding Inspections

Case Number: T08FR04449
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
11/26/2008 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings
11/26/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove/Replace with approved power strip.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04449
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
11/26/2008 INSP - FULL JLOYA Approved Correct the following violations found 11-25-08 during fire inspection for recomendation into self inspection program.
01/12/2009 INSP - REINSPECTION JLOYA Approved All violations abated.