Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T08FR04399
Case Details
Entered Date:
11/21/2008
Applicant:
LOS TRES ABOGADOS LLC
Description:
SPRINKLER INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04399
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2008 | INSP - FULL | EDESCHAI | Approved | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. IF THE CORRECTIONS HAVE BEEN MADE PLEASE FORWARD A COPY OF THE CORRECTION REPORT. 1) THE SPARE HEAD BOX REQUIRES 2 ADDITIONAL 155 DEGREE QUICK RESPONSE HEADS 2) COVER PLATES THAT ARE MISSING SHALL BE REPLACED ON THE CONCEALED SPRINKLER HEADS. 3) A SURVEY SHALL BE DONE ON THE CONCEALED SPRINKLER HEADS, IF THEY ARE AMONG THOSE THAT WERE RECALLED BY THE CENTRAL COMPANY, THEY SHALL BE REPLACED |