Case: T08FR04399

Parcel: 113052600


Addresses:

3503 N CAMPBELL AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR04399

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
03/24/2009 INSP - FULL Approved
02/10/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 11-21-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 3503 N. CAMPBELL. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
11/21/2008 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. IF THE CORRECTIONS HAVE BEEN MADE PLEASE FORWARD A COPY OF THE CORRECTION REPORT.

1) THE SPARE HEAD BOX REQUIRES 2 ADDITIONAL 155 DEGREE QUICK RESPONSE HEADS

2) COVER PLATES THAT ARE MISSING SHALL BE REPLACED ON THE CONCEALED SPRINKLER HEADS.

3) A SURVEY SHALL BE DONE ON THE CONCEALED SPRINKLER HEADS, IF THEY ARE AMONG THOSE THAT WERE RECALLED BY THE CENTRAL COMPANY, THEY SHALL BE REPLACED