Case: T08FR04358
Case Details
Entered Date:
11/18/2008
Applicant:
GRANT & ALVERNON REALTY TR
Description:
SPRINKLER INSPECTION
Completed Inspections
Case Status: FIELD
Case Number: T08FR04358
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/18/2008 | INSP - FULL | EDESCHAI | Approved | DURING THE LAST ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. IF CORRECTIONS HAVE BEEN DONE PLEASE SEND A COPY OF THE CORRECTION MANIFEST 1) REPLACE MISSING CAPS ON THE FIRE DEPARTMENT CONNECTION 2) THE SPARE HEAD BOX NEEDS A CENTRAL-A, 165 DEGREE BRASS STANDARD SPRAY PENDANT HEAD 3) IF THE CONTROL VALVE IS NOT IN A SECURE AREA IT SHALL BE ELECTRONICALY SUPERVISED OR LOCKED AND CHAINED IN THE OPEN POSITION |