Case: T08FR04358

Parcel: 12201024G


Addresses:

3938 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR04358

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/18/2009 INSP - FULL Approved
02/03/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 11-18-2008, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT
3938 E. GRANT RD. IF CORRECTED, HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
11/18/2008 INSP - FULL Correction Required DURING THE LAST ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. IF CORRECTIONS HAVE BEEN DONE PLEASE SEND A COPY OF THE CORRECTION MANIFEST

1) REPLACE MISSING CAPS ON THE FIRE DEPARTMENT CONNECTION

2) THE SPARE HEAD BOX NEEDS A CENTRAL-A, 165 DEGREE BRASS STANDARD SPRAY PENDANT HEAD

3) IF THE CONTROL VALVE IS NOT IN A SECURE AREA IT SHALL BE ELECTRONICALY SUPERVISED OR LOCKED AND CHAINED IN THE OPEN POSITION