Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T08FR04157
Case Details
Entered Date:
11/04/2008
Applicant:
MARSHALL FOUNDATION
Description:
SPRINKLER INSPECTION
Outstanding Inspections
Case Number: T08FR04157
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2008 | INSP - FULL | EDESCHAI | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH ION 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) STORAGE IS LOCATED TO CLOSE TO SPRINKLERS AT SUITE # 216 AND # 225A AND BY THE SECOND FLOOR COPY AREA. A MINIMUM OF 18 INCHES SHALL BE MAINTAINED BELOW SPRINKLER HEADS 2) ROOM #225A HAS TWO SPRINKLER HEADS THAT ARE LESS THAN THE REQUIRED 6 FEET APART. 3) IT IS RECOMENDED THAT TEAD GUARDS BE INSTALLED IN THE FOLLOWING AREAS, SECOND FLOOR STORE ROOM # 223, THE AULD DUBLINER PUB IN THE HALL, IN THE PRIVATE AREA AND AT THE LOW BAR AREA. |