Case: T08FR04157

Parcel: 124050520


Addresses:

800 E UNIVERSITY BL


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T08FR04157

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
11/04/2008 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH ION 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE.

1) STORAGE IS LOCATED TO CLOSE TO SPRINKLERS AT SUITE # 216 AND # 225A AND BY THE SECOND FLOOR COPY AREA. A MINIMUM OF 18 INCHES SHALL BE MAINTAINED BELOW SPRINKLER HEADS

2) ROOM #225A HAS TWO SPRINKLER HEADS THAT ARE LESS THAN THE REQUIRED 6 FEET APART.