Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)
Address:

Entered Date:

11/03/2008

Applicant:

SISTERS OF ST JOSEPH IN ARIZ

Description:

SPRINKLER INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04136
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/03/2008 INSP - FULL EDESCHAI Approved ENCLOSED PLEASE FIND A COPY OF THE LAST SPRINKLER INSPECTION. THE FOLLOWING DEFICIENCY WAS FOUND AN SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE SPRINKLER IN THE RISER ROOM EXCEEDS THE MAXIMUM ALLOWABLE DISTANCE FROM THE CEILING AND SHALL BE SHORTENED 2) IF GUAGES ON THE RISER CANNOT BE CALIBRARED THEN THEY SHALL BE REPLACED 3) PROVIDE A LOCK FOR THE POST INDICATOR VALVE, IT WAS ALSO STUCK IN THE OPEN POSITION AND SHALL BE REPAIRED 4) CHECK WITH THE INSPECTING CONTRACTOR ON THE FOLLOWING ITEMS, UNABLE TO DETERMINE WRITE UP: A) A TOTAL OF 5 HEADS NEED REPLACING B) NEED MAIN CONTROL VALVE ON P. I. V.