Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR04136
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2009 | INSP - FULL | Approved | CONTRACTORS CORRECTION REPORT TO SYSTEMS | |
11/03/2008 | INSP - FULL | Correction Required | ENCLOSED PLEASE FIND A COPY OF THE LAST SPRINKLER INSPECTION. THE FOLLOWING DEFICIENCY WAS FOUND AN SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE SPRINKLER IN THE RISER ROOM EXCEEDS THE MAXIMUM ALLOWABLE DISTANCE FROM THE CEILING AND SHALL BE SHORTENED 2) IF GUAGES ON THE RISER CANNOT BE CALIBRARED THEN THEY SHALL BE REPLACED 3) PROVIDE A LOCK FOR THE POST INDICATOR VALVE, IT WAS ALSO STUCK IN THE OPEN POSITION AND SHALL BE REPAIRED 4) CHECK WITH THE INSPECTING CONTRACTOR ON THE FOLLOWING ITEMS, UNABLE TO DETERMINE WRITE UP: A) A TOTAL OF 5 HEADS NEED REPLACING B) NEED MAIN CONTROL VALVE ON P. I. V. |