Case: T08FR04136

Parcel: 133170600


Addresses:

410 N WILMOT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR04136

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
07/15/2009 INSP - FULL Approved CONTRACTORS CORRECTION REPORT TO SYSTEMS
11/03/2008 INSP - FULL Correction Required ENCLOSED PLEASE FIND A COPY OF THE LAST SPRINKLER INSPECTION. THE FOLLOWING DEFICIENCY WAS FOUND AN SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE.

1) THE SPRINKLER IN THE RISER ROOM EXCEEDS THE MAXIMUM ALLOWABLE DISTANCE FROM THE CEILING AND SHALL BE SHORTENED

2) IF GUAGES ON THE RISER CANNOT BE CALIBRARED THEN THEY SHALL BE REPLACED

3) PROVIDE A LOCK FOR THE POST INDICATOR VALVE, IT WAS ALSO STUCK IN THE OPEN POSITION AND SHALL BE REPAIRED

4) CHECK WITH THE INSPECTING CONTRACTOR ON THE FOLLOWING ITEMS, UNABLE TO DETERMINE WRITE UP:
A) A TOTAL OF 5 HEADS NEED REPLACING
B) NEED MAIN CONTROL VALVE ON P. I. V.