SPRINKLER INSPECTION

Completed Inspections

Case Status: FIELD
Case Number: T08FR04027
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/29/2008 INSP - FULL EDESCHAI Approved DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. PLEASE FORWARD A COPY OF THE REPAIR MANIFEST TO THIS OFFICE 1) THE ALARM VALVE IS DUE FOR THE 5 YEAR INTERNAL VALVE INSPECTION 2) INSTALL AN INSPECTORS TEST TO ALLOW FOR VERIFICATION OF WATER FLOW AND VERIFICATION 3) IMMEDIATE ACCESS TO THE SPRINKLER RISER SHALL BE PROVIDED, A DESK NEEDS TO BE RELOCATED