Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2009 | INSP - FULL | Approved | ||
| 10/29/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. PLEASE FORWARD A COPY OF THE REPAIR MANIFEST TO THIS OFFICE 1) THE ALARM VALVE IS DUE FOR THE 5 YEAR INTERNAL VALVE INSPECTION 2) INSTALL AN INSPECTORS TEST TO ALLOW FOR VERIFICATION OF WATER FLOW AND VERIFICATION 3) IMMEDIATE ACCESS TO THE SPRINKLER RISER SHALL BE PROVIDED, A DESK NEEDS TO BE RELOCATED |