Case: T08FR04027

Parcel: 10819297A


Addresses:

4578 N 1ST AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR04027

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
01/22/2009 INSP - FULL Approved
10/29/2008 INSP - FULL Correction Required DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. PLEASE FORWARD A COPY OF THE REPAIR MANIFEST TO THIS OFFICE

1) THE ALARM VALVE IS DUE FOR THE 5 YEAR INTERNAL VALVE INSPECTION

2) INSTALL AN INSPECTORS TEST TO ALLOW FOR VERIFICATION OF WATER FLOW AND VERIFICATION

3) IMMEDIATE ACCESS TO THE SPRINKLER RISER SHALL BE PROVIDED, A DESK NEEDS TO BE RELOCATED