Case: T08FR04026
Case Details
Entered Date:
10/29/2008
Applicant:
WG ENTERPRISES LLC
Description:
SPRINKLER INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04026
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/29/2008 | INSP - FULL | EDESCHAI | Approved | DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. PLEASE PROVIDE THIS OFFICE WITH A COPY OF THE REPAIR MANIFEST. 1) THE CONTROL VALVE SHALL BE SECURED WITH A LOCK AND CHAIN 2) THE ALARM VALVE IS DUE FOR THE 5 YEAR INTERNAL VALVE INSPECTION 3) THE BUSHES AROUND THE FFIRE DEPARTMENT CONNECTION SHALL BE TRIMMED FOR A 3 FOOT CLEARANCE TO PROVIDE ACCESSABILITY 4) INSTALL ACOVER ON THE FLOW SWITCH |