Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)
Address:

Entered Date:

10/29/2008

Applicant:

WG ENTERPRISES LLC

Description:

SPRINKLER INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04026
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/29/2008 INSP - FULL EDESCHAI Approved DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. PLEASE PROVIDE THIS OFFICE WITH A COPY OF THE REPAIR MANIFEST. 1) THE CONTROL VALVE SHALL BE SECURED WITH A LOCK AND CHAIN 2) THE ALARM VALVE IS DUE FOR THE 5 YEAR INTERNAL VALVE INSPECTION 3) THE BUSHES AROUND THE FFIRE DEPARTMENT CONNECTION SHALL BE TRIMMED FOR A 3 FOOT CLEARANCE TO PROVIDE ACCESSABILITY 4) INSTALL ACOVER ON THE FLOW SWITCH