Case: T08FR04026

Parcel: 108192870


Addresses:

4574 N 1ST AV

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
01/22/2009 INSP - FULL Approved
10/29/2008 INSP - FULL Correction Required DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. PLEASE PROVIDE THIS OFFICE WITH A COPY OF THE REPAIR MANIFEST.

1) THE CONTROL VALVE SHALL BE SECURED WITH A LOCK AND CHAIN

2) THE ALARM VALVE IS DUE FOR THE 5 YEAR INTERNAL VALVE INSPECTION

3) THE BUSHES AROUND THE FFIRE DEPARTMENT CONNECTION SHALL BE TRIMMED FOR A 3 FOOT CLEARANCE TO PROVIDE ACCESSABILITY

4) INSTALL ACOVER ON THE FLOW SWITCH