Case: T08FR04010
Case Details
Entered Date:
10/28/2008
Applicant:
BLAKE ROBERT E & DEBORAH L CP/RS
Description:
FULL FIRE INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04010
Case Description: INSPECTION
Total Completed Inspections - 13
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 13.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT IN WEST DANCE FLOOR MUST BE SERVICED/REPAIRED SO THAT IT ILLUMINATES PROPERLY. |
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 12.) TFC 901.6.2 THE AUTOMATIC SPRINKLER SYSTEM IS PAST DUE FOR ANNUAL INSPECTION. HAVE THE SYSTEM INSPECTED AND CORRECT ANY NOTED DISCREPANCIES. |
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 11.) TFC 906.2 PORTABLE FIRE EXTINGUISHER UPSTAIRS IS PAST DUE FOR ANNUAL INSPECTION. |
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 10.) TFC 703.1.1 THE HOLE IN THE SHEETROCK OF THE CEILING UPSTAIRS MUST REPAIRED TO MAINTAIN REQUIRED FIREBLOCKING AND DRAFTSTOPPING. |
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 9.) TFC 605.5 THE EXTENSION CORDS IN THE SOUND EQUIPMENT AREA OF EAST DANCE FLOOR ARE NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 8.) TFC 605.6 THE ELECTRICAL OUTLET IN THE SOUND EQUIPMENT AREA OF EAST DANCE FLOOR MUST HAVE A COVER PLATE INSTALLED. |
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 7.) TFC 605.6 THE ELECTRICAL JUNCTION BOX OUTSIDE OF THE MEN'S DRESSING ROOM MUST HAVE A COVER PLATE INSTALLED. |
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 6.) TFC 605.5 THE EXTENSION CORD OUTSIDE OF MEN'S DRESSING ROOM IS NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 5.) TFC 901.4.1 THE CLOTHING HANGING ON SPRINKLER PIPE IN CLOSET OF BACK ROOM IS BLOCKING SPRINKLER HEAD AND MSUT BE REMOVED. |
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 4.) TFC 703.1.1 THE MISSING CEILING TILE IN BACK ROOM MUST BE REPLACED TO MAINTAIN REQUIRED FIREBLOCKING AND DRAFTSTOPPING. |
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 3.) TFC 906.2 PORTABLE FIRE EXTINGUISHER IN KITCHEN MUST HAVE A CURRENT INSPECTION TAG. |
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 2.) TFC 901.4 SPRINKLER HEADS IN OFFICE AT END OF HALLWAY CANNOT BE OF DIFFERENT TYPES. |
| 10/28/2008 | INSP - FULL | RSPANGLE | Approved | 1.) TFC 510.1 RISER ROOM MUST HAVE A SIGN INSTALLED. |