Case: T08FR04010

Parcel: 11007233D


Addresses:

4101 E GRANT RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
01/15/2009 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. THE SPRINKLER SYSTEM INSP. REPORT AND REPAIR BILLING INVOICE HAVE BEEN SUBMITTED.
10/28/2008 INSP - FULL Violation 1.) TFC 510.1 RISER ROOM MUST HAVE A SIGN INSTALLED.
10/28/2008 INSP - FULL Violation 2.) TFC 901.4 SPRINKLER HEADS IN OFFICE AT END OF HALLWAY CANNOT BE OF DIFFERENT TYPES.
10/28/2008 INSP - FULL Violation 3.) TFC 906.2 PORTABLE FIRE EXTINGUISHER IN KITCHEN MUST HAVE A CURRENT INSPECTION TAG.
10/28/2008 INSP - FULL Violation 4.) TFC 703.1.1 THE MISSING CEILING TILE IN BACK ROOM MUST BE REPLACED TO MAINTAIN REQUIRED FIREBLOCKING AND DRAFTSTOPPING.
10/28/2008 INSP - FULL Violation 5.) TFC 901.4.1 THE CLOTHING HANGING ON SPRINKLER PIPE IN CLOSET OF BACK ROOM IS BLOCKING SPRINKLER HEAD AND MSUT BE REMOVED.
10/28/2008 INSP - FULL Violation 6.) TFC 605.5 THE EXTENSION CORD OUTSIDE OF MEN'S DRESSING ROOM IS NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING.
10/28/2008 INSP - FULL Violation 7.) TFC 605.6 THE ELECTRICAL JUNCTION BOX OUTSIDE OF THE MEN'S DRESSING ROOM MUST HAVE A COVER PLATE INSTALLED.
10/28/2008 INSP - FULL Violation 8.) TFC 605.6 THE ELECTRICAL OUTLET IN THE SOUND EQUIPMENT AREA OF EAST DANCE FLOOR MUST HAVE A COVER PLATE INSTALLED.
10/28/2008 INSP - FULL Violation 9.) TFC 605.5 THE EXTENSION CORDS IN THE SOUND EQUIPMENT AREA OF EAST DANCE FLOOR ARE NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING.
10/28/2008 INSP - FULL Violation 10.) TFC 703.1.1 THE HOLE IN THE SHEETROCK OF THE CEILING UPSTAIRS MUST REPAIRED TO MAINTAIN REQUIRED FIREBLOCKING AND DRAFTSTOPPING.
10/28/2008 INSP - FULL Violation 11.) TFC 906.2 PORTABLE FIRE EXTINGUISHER UPSTAIRS IS PAST DUE FOR ANNUAL INSPECTION.
10/28/2008 INSP - FULL Violation 12.) TFC 901.6.2 THE AUTOMATIC SPRINKLER SYSTEM IS PAST DUE FOR ANNUAL INSPECTION. HAVE THE SYSTEM INSPECTED AND CORRECT ANY NOTED DISCREPANCIES.
10/28/2008 INSP - FULL Violation 13.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT IN WEST DANCE FLOOR MUST BE SERVICED/REPAIRED SO THAT IT ILLUMINATES PROPERLY.