Case Details

Status:

FIELD

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

10/28/2008

Applicant:

ATRIUM CENTER #1 LTD PARTNERSHIP

Description:

SPRINKLER INSPECTION

Outstanding Inspections

Case Number: T08FR04002
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
10/28/2008 INSP - FULL EDESCHAI Correction Required DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS 1) SUITE 102 / 103 (VACANT) SPRINKLER PROTECTION SHALL BE ADDED TO THE CLOSET IN THE FRONT OFFICE. 2) AN IDENTIFICATION SIGN SHALL BE POSTED ON THE INSPECTORS TEST VALVE. 3) IF THE MAIN CONTROL VALVE FOR THE SPRINKLER SYSTEM IS NOT IN A SECURE AREA IT SHALL BE PROVIDED A LOCK AND CHAIN 4) THE SPARE HEAD BOX SHALL BE PROVIDED AN ADDITIONAL 1/2 INCH, 165 DEGREE, PENDANT HEAD