Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/23/2008

Applicant:

PARK MALL LLC

Description:

Orange Julius #140, initial inspection 10/16/08

Outstanding Inspections

Case Number: T08FR03925
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
10/23/2008 INSP - FULL DGREENLE Correction Required Full inspection conducted 10/16/08. Please correct the following items.
10/23/2008 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. _____ Maintain 18 inch clearance below the deflectors of all sprinkler heads, including the one in the freezer.
10/23/2008 VIOL - MEANS OF EGRESS DGREENLE Correction Required 1008.1.8 Door operations. ...egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. TFC 1008.1.8.4 - Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove bolt locks from door out of service area. Any lock on this door must be openable from the service area side.
10/27/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Remove multi-plug adaptor - service area ceiling

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03925
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/23/2009 COMPLIANCE DGREENLE Approved appeal approved by Chief Uthe to keep slide bolt locks