Case: T08FR03925
Case Details
Entered Date:
10/23/2008
Applicant:
PARK MALL LLC
Description:
Orange Julius #140, initial inspection 10/16/08
Outstanding Inspections
Case Number: T08FR03925
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/23/2008 | INSP - FULL | DGREENLE | Correction Required | Full inspection conducted 10/16/08. Please correct the following items. |
10/23/2008 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Correction Required | TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. _____ Maintain 18 inch clearance below the deflectors of all sprinkler heads, including the one in the freezer. |
10/23/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Correction Required | 1008.1.8 Door operations. ...egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. TFC 1008.1.8.4 - Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove bolt locks from door out of service area. Any lock on this door must be openable from the service area side. |
10/27/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Remove multi-plug adaptor - service area ceiling |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR03925
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2009 | COMPLIANCE | DGREENLE | Approved | appeal approved by Chief Uthe to keep slide bolt locks |