Case: T08FR03925

Parcel: 12801005H

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR03925

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
10/23/2008 VIOL - MEANS OF EGRESS Correction Required 1008.1.8 Door operations. ...egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
TFC 1008.1.8.4 - Bolt locks. Manually operated flush bolts or surface bolts are not permitted.

_____ Remove bolt locks from door out of service area. Any lock on this door must be openable from the service area side.