Verizon Wireless #102, Full inspection conducted 10/8/08
Outstanding Inspections
Case Number: T08FR03597
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
10/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | Power tap design. TFC 605.4.1 - Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. _____ extension cord servicing microwave and paper shredder |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR03597
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2008 | INSP - FULL | DGREENLE | Approved | No Certificate of Occupany on file, Occupant shall obtain current C of O |
11/03/2008 | COMPL - REINSPECTION | DGREENLE | Approved |