Case: T08FR03597

Parcel: 12801005H

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T08FR03597

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
10/08/2008 VIOL - BUILDING SVCS & SYSTEMS Violation Blocked electrical panel:
TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.

_____ Clear area around electrical panels and transformer.
10/08/2008 VIOL - BUILDING SVCS & SYSTEMS Violation Power tap design.
TFC 605.4.1 - Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363.

_____ extension cord servicing microwave and paper shredder