Case: T08FR03520
Case Details
Entered Date:
10/03/2008
Applicant:
ARIZONA BOARD OF REGENTS
Description:
FULL FIRE INSPECTION.
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR03520
Case Description: INSPECTION
Total Completed Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2008 | VIOL - MEANS OF EGRESS | JVINCENT | Approved | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1028.8 Panic Hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door... ____The green button on the side of the front door is considered special knowledge. The panic hardware must disengage the magnetic lock without having to press the button. ____Remove the double-keyed deadbolt from the front door. No other locking mechanism is allowed on a door with panic hardware. |
| 10/03/2008 | VIOL - MEANS OF EGRESS | JVINCENT | Approved | 1027.5 Illumination emergency power. ____Repair emergency lighting units: ____Lighting unit in stairwell leading to chapter room. ____Lighing units outside sleeping porch doors on 2nd and 3rd floor. |
| 10/03/2008 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Approved | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Test all battery powered smoke detectors. Maintenance Log included with this report. Complete and provide upon re-inspection. |
| 10/03/2008 | VIOL - MEANS OF EGRESS | JVINCENT | Approved | 1024.6 Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way. ____The means of egress needs to be unobstructed at all times. Do not obstruct the East Exit with bicylcles. |
| 10/03/2008 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Approved | 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. ____Kitchen hood extinguishing system due for 6 month inspection. |
| 10/03/2008 | VIOL - FIRE SERVICE FEATURES | JVINCENT | Approved | 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. ____Label riser room door. "RISER ROOM" |
| 10/03/2008 | VIOL - EMERGENCY PLAN/PREPARE | JVINCENT | Approved | 405.2 Frequency. Required emergency evacuation drills shall be held at the intervals specified in Table 405.2 or more frequently where necessary to familiarize all occupants with the drill procedure. ____Four Evacuation Drills required annually. Keep records on-site. |
| 10/03/2008 | INSP - FULL | JVINCENT | Approved | FULL FIRE INSPECTION. |