Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T08FR03520
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2009 | VIOL - MEANS OF EGRESS | Approved | ||
| 10/03/2008 | VIOL - MEANS OF EGRESS | Violation | 1024.6 Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way. ____The means of egress needs to be unobstructed at all times. Do not obstruct the East Exit with bicylcles. |
|
| 10/03/2008 | VIOL - MEANS OF EGRESS | Violation | 1027.5 Illumination emergency power. ____Repair emergency lighting units: ____Lighting unit in stairwell leading to chapter room. ____Lighing units outside sleeping porch doors on 2nd and 3rd floor. |
|
| 10/03/2008 | VIOL - MEANS OF EGRESS | Violation | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1028.8 Panic Hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door... ____The green button on the side of the front door is considered special knowledge. The panic hardware must disengage the magnetic lock without having to press the button. ____Remove the double-keyed deadbolt from the front door. No other locking mechanism is allowed on a door with panic hardware. |