Case: T08FR03520

Parcel: 12404003B


Addresses:

1420 E 1ST ST


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR03520

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
05/13/2009 VIOL - MEANS OF EGRESS Approved
10/03/2008 VIOL - MEANS OF EGRESS Violation 1024.6 Access to a public way. The exit discharge shall provide
a direct and unobstructed access to a public way.

____The means of egress needs to be unobstructed at all times. Do not obstruct the East Exit with bicylcles.
10/03/2008 VIOL - MEANS OF EGRESS Violation 1027.5 Illumination emergency power.

____Repair emergency lighting units:
____Lighting unit in stairwell leading to chapter room.
____Lighing units outside sleeping porch doors on 2nd and 3rd floor.
10/03/2008 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

1028.8 Panic Hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door...

____The green button on the side of the front door is considered special knowledge. The panic hardware must disengage the magnetic lock without having to press the button.
____Remove the double-keyed deadbolt from the front door. No other locking mechanism is allowed on a door with panic hardware.