Case: T08FR03435
Case Details
Entered Date:
10/01/2008
Applicant:
Y CREEK INVESTMENTS LLC
Description:
ACRC - sprinkler test required; Full inspection done 9/15/09 ; "B" occupancy; Krissa Goodin / Jill Vilches - 290-2510 Common ground by Chapman Management Annette Rawls 622-5544 / Kazal Fire handling systems.
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR03435
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2008 | INSP - FULL | ALOPEZ | Approved | Sprinkler test full inspection required: Please correct the following Tucson Fire Code violations: Notes: 1. Cof O to be provided upon re-inspection, if available. If not available, manager will be in the process of acquiring it. Certificate of Occupancy [C of O]: 1997 Uniform Administrative Code Section 309.5 Posting. The certificate of occupancy shall be posted in a conspicuous place on the premises and shall not be removed except by the building official. ______ Acquire a C of O from Developmental Services. [791-5550] ______ C of O on site. 2. A record of the sprinkler system inspections shall be made available upon re-inspection. |
| 09/16/2009 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Approved | Fire Department connection: 912.2.2 Existing buildings. On existing buildings, wherever the fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters "FDC" at least 6 inches (152 mm) high and words in letters at least 2 inches (51 mm) high or an arrow to indicate the location. All such signs shall be subject to the approval of the fire code official. ______ Place approved sign stating or pointing FDC is in back of building. Please keep a copy of this report for your files for future reference. The sprinklers require annual testing and inspecting and a copy of report shall be available on the premises. 912.3 Access. Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or any other object for a minimum of 3 feet (914 mm). ______ Remove excess growth assuring access to the FDC and maintain it this way. |