Case: T08FR03435

Parcel: 13315349A


Addresses:

1825 N KOLB RD


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR03435

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
08/20/2010 VIOL - FIRE PROTECTION SYSTEMS Approved All approved / closed
09/16/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Fire Department connection:
912.2.2 Existing buildings. On existing buildings, wherever
the fire department connection is not visible to
approaching fire apparatus, the fire department connection
shall be indicated by an approved sign mounted on the street
front or on the side of the building. Such sign shall have the
letters "FDC" at least 6 inches (152 mm) high and words in
letters at least 2 inches (51 mm) high or an arrow to indicate
the location. All such signs shall be subject to the approval
of the fire code official.

______ Place approved sign stating or pointing FDC is in back of building.

Please keep a copy of this report for your files for future reference.
The sprinklers require annual testing and inspecting and a copy of report shall be available on the premises.




912.3 Access. Immediate access to fire department connections
shall be maintained at all times and without obstruction
by fences, bushes, trees, walls or any other object for a minimum
of 3 feet (914 mm).

______ Remove excess growth assuring access to the FDC and maintain it this way.