Description:

Full inspection performed 9/30/08

Outstanding Inspections

Case Number: T08FR03399
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
10/01/2008 VIOL - PRECAUTION AGAINST FIRE DGREENLE Violation TFC 315.2.2 - Means of egress. Combustible materials shall not be stored in exits or exit enclosures. _____ Keep back exit hallway accssable and clear (32") even during stocking.
10/01/2008 VIOL - PRECAUTION AGAINST FIRE DGREENLE Violation MISCELLANEOUS COMBUSTIBLE MATERIALS STORAGE TFC 315.2.1 - Ceiling clearance. Storage shall be maintained ... a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. _____ Keep stockroom shelving clear 18" below sprinkler heads. (against walls it's ok to go higher)
10/01/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. ... Extension cords shall be used only with portable appliances. _____ remove extension cord and plug powerstrip (under stockroom desk) directly into outlet
10/01/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panel and transformer.
10/01/2008 VIOL - MEANS OF EGRESS DGREENLE Violation Blocked exit: TFC 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.
10/15/2008 INSP - REINSPECTION DGREENLE Continued - CONTINUED next RI 10/30

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03399
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
10/01/2008 INSP - FULL DGREENLE Approved Certificate of Occupancy: ON FILE & POSTED Batteries on some EXIT signs and Emergency lights are starting to fail, replace soon. Extinguishers Serviced and Tagged (4/08) - Occupant shall perform monthly inspections and indicate such on tag. Remember to keep extinguishers unobscured and unobstructed.
11/03/2008 COMPL - REINSPECTION DGREENLE Approved