Case: T08FR03399

Parcel: 12801005H

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T08FR03399

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
10/01/2008 VIOL - BUILDING SVCS & SYSTEMS Violation Blocked electrical panel:
TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.

_____ Clear area in front of electrical panel and transformer.
10/01/2008 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.

TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. ... Extension cords shall be used only with portable appliances.

_____ remove extension cord and plug powerstrip (under stockroom desk) directly into outlet