Case: T08FR03322
Case Details
Entered Date:
09/30/2008
Applicant:
BUILDER S FASHION SQUARE LLC
Description:
FULL FIRE INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR03322
Case Description: INSPECTION
Total Completed Inspections - 13
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/30/2008 | INSP - FULL | RSPANGLE | Approved | 10) TFC 605.6 IN THE STORAGE ROOM NEXT TO ROOM 10 THE ELECTRICAL OUTLET ON THE CEILING NEEDS A COVER PLATE INSTALLED. |
09/30/2008 | INSP - FULL | RSPANGLE | Approved | NOTE: HAVE EMERGENCY ILLUMINATION UNITS NEAR THE CEILING THROUGHOUT THE FACILITY TESTED AND VERIFY THAT THEY ARE OPERATIONAL. |
09/30/2008 | INSP - FULL | RSPANGLE | Approved | 7.) TFC 3404.3.6.3 FLAMMABLE LIQUIDS MUST BE KEPT SEPARATED FROM COMBUSTIBLE STORAGE IN PAINT STORAGE AREA. |
09/30/2008 | INSP - FULL | RSPANGLE | Approved | 12.) TFC 903.3.7 THE FIRE DEPT. CONNECTIONS FACING SPEEDWAY MUST BE PAINTED RED. |
09/30/2008 | INSP - FULL | RSPANGLE | Approved | 11.) TFC 605.6 THE EXTENSION CORD IN STUDIO "A" OFFICE IS NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING. |
09/30/2008 | INSP - FULL | RSPANGLE | Approved | 9.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT IN STUDIO "A" IS NOT WORKING. HAVE UNIT REPAIRED OR REPLACED. |
09/30/2008 | INSP - FULL | RSPANGLE | Approved | 8.) TFC 605.6 THE OPEN WIRE SPLICE IN THE POWER CORD FOR THE ELECTRIC FAN IN THE MAINTENANCE CLOSET IS NOT PERMITTED BY THE FIRE CODE. |
09/30/2008 | INSP - FULL | RSPANGLE | Approved | 6.) TFC 605.6 TWO ELECTRICAL JUNCTION BOXES NEAR THE CEILING IN THE JANITOR'S ROOM MUST HAVE COVER PLATES INSTALLED. |
09/30/2008 | INSP - FULL | RSPANGLE | Approved | 5.) TFC 605.6 THE LIGHT SWITCH IN THE JANITOR'S ROOM MUST HAVE A PROPER COVER PLATE INSTALLED. |
09/30/2008 | INSP - FULL | RSPANGLE | Approved | 4.0 TFC 605.6 THE BROKEN OUTLET COVER PLATE IN THE JANITOR'S ROOM MUST BE REPLACED. |
09/30/2008 | INSP - FULL | RSPANGLE | Approved | 3.) TFC 605.6 THE ELECTRICAL JUNCTION BOX MOUNTED ON TOP OF THE NORTH WALL OF NURSERY IS REQUIRED TO HAVE A COVER PLATE INSTALLED. |
09/30/2008 | INSP - FULL | RSPANGLE | Approved | 2.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER IN THE NURSERY OFFICE IS PAST DUE FOR ANNUAL INSPECTION. HAVE EXTINGUISHER INSPECTED. |
09/30/2008 | INSP - FULL | RSPANGLE | Approved | 1.) TFC 901.6.2 RECORDS OF ALL SPRINKLER SYSTEM INSPECTIONS, TESTS AND MAINTENANCE SHALL BE MAINTAINED ON THE PREMISES FOR A MIN. OF 3 YEARS. SHOW PROOF OF ANNUAL INSPECTION OR HAVE SPRINKLER SYSTEM INSPECTED AND NOTED DISCREPANCIES REPAIRED. |