Case: T08FR03322

Parcel: 12106001B


Addresses:

5851 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
01/15/2009 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
NOTE: THE SPRINKLER SYSTEM HAS BEE INSPECTED WITH REPAIRS REQUIRED. ED DESCHAINES WILL FOLLOW UP TO INSURE COMPLETION OF REPAIRS.
09/30/2008 INSP - FULL Violation 1.) TFC 901.6.2 RECORDS OF ALL SPRINKLER SYSTEM INSPECTIONS, TESTS AND MAINTENANCE SHALL BE MAINTAINED ON THE PREMISES FOR A MIN. OF 3 YEARS. SHOW PROOF OF ANNUAL INSPECTION OR HAVE SPRINKLER SYSTEM INSPECTED AND NOTED DISCREPANCIES REPAIRED.
09/30/2008 INSP - FULL Violation 2.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER IN THE NURSERY OFFICE IS PAST DUE FOR ANNUAL INSPECTION. HAVE EXTINGUISHER INSPECTED.
09/30/2008 INSP - FULL Violation 3.) TFC 605.6 THE ELECTRICAL JUNCTION BOX MOUNTED ON TOP OF THE NORTH WALL OF NURSERY IS REQUIRED TO HAVE A COVER PLATE INSTALLED.
09/30/2008 INSP - FULL Violation 4.0 TFC 605.6 THE BROKEN OUTLET COVER PLATE IN THE JANITOR'S ROOM MUST BE REPLACED.
09/30/2008 INSP - FULL Violation 5.) TFC 605.6 THE LIGHT SWITCH IN THE JANITOR'S ROOM MUST HAVE A PROPER COVER PLATE INSTALLED.
09/30/2008 INSP - FULL Violation 6.) TFC 605.6 TWO ELECTRICAL JUNCTION BOXES NEAR THE CEILING IN THE JANITOR'S ROOM MUST HAVE COVER PLATES INSTALLED.
09/30/2008 INSP - FULL Violation 8.) TFC 605.6 THE OPEN WIRE SPLICE IN THE POWER CORD FOR THE ELECTRIC FAN IN THE MAINTENANCE CLOSET IS NOT PERMITTED BY THE FIRE CODE.
09/30/2008 INSP - FULL Violation 9.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT IN STUDIO "A" IS NOT WORKING. HAVE UNIT REPAIRED OR REPLACED.
09/30/2008 INSP - FULL Violation 11.) TFC 605.6 THE EXTENSION CORD IN STUDIO "A" OFFICE IS NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING.
09/30/2008 INSP - FULL Violation 12.) TFC 903.3.7 THE FIRE DEPT. CONNECTIONS FACING SPEEDWAY MUST BE PAINTED RED.
09/30/2008 INSP - FULL Violation 7.) TFC 3404.3.6.3 FLAMMABLE LIQUIDS MUST BE KEPT SEPARATED FROM COMBUSTIBLE STORAGE IN PAINT STORAGE AREA.
09/30/2008 INSP - FULL Violation NOTE: HAVE EMERGENCY ILLUMINATION UNITS NEAR THE CEILING THROUGHOUT THE FACILITY TESTED AND VERIFY THAT THEY ARE OPERATIONAL.
09/30/2008 INSP - FULL Violation 10) TFC 605.6 IN THE STORAGE ROOM NEXT TO ROOM 10 THE ELECTRICAL OUTLET ON THE CEILING NEEDS A COVER PLATE INSTALLED.