Description:

FULL FIRE INSPECTION.

Outstanding Inspections

Case Number: T08FR03117
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
09/25/2008 INSP - FULL JVINCENT Violation FULL FIRE INSPECTION.
09/25/2008 VIOL - EMERGENCY PLAN/PREPARE JVINCENT Violation 405.2 Frequency. Required emergency evacuation drills shall be held at the intervals specified in Table 405.2 or more frequently where necessary to familiarize all occupants with the drill procedure. ____Four Evacuation Drills required annually. Keep records on-site.
09/25/2008 VIOL - FIRE SERVICE FEATURES JVINCENT Violation 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. ____Post address on building per Pima County Address Requirements.
09/25/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Test all smoke detectors in bedrooms and halls. Provide documentation upon reinspection.
09/25/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. ____Have the hood system professionally cleaned. Last cleaning was in 2000.
09/25/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. ____Commercial cooking extinguishig system due for inspection/service.
09/25/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Extinguishers due for annual inspection/service.
09/25/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation TFC 903.2.7 Group R. Existing sorority and fraternity house and existing Group R-4 occupancies shall have automatic sprinkler systems installed. A permit shall be issued within two years of the adoption of this code and the work shall be completed within three years of the adoption of this code. ____Sprinkler system required by October 22, 2010.
09/25/2008 VIOL - MEANS OF EGRESS JVINCENT Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ____Remove keyed lock from kitchen exit security door. Thumb-turn lock OK.