Case: T08FR03117

Parcel: 117033520


Addresses:

638 E UNIVERSITY BL


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR03117

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
09/25/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall
be selected, installed and maintained in accordance with this
section and NFPA 10.

____Extinguishers due for annual inspection/service.
09/25/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.4 Extinguishing system service. Automatic
fire-extinguishing systems shall be serviced at least
every 6 months and after activation of the system.

____Commercial cooking extinguishig system due for inspection/service.
09/25/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.3 Cleaning. Hoods, grease-removal devices,
fans, ducts and other appurtenances shall be cleaned at
intervals necessary to prevent the accumulation of
grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records
shall be maintained on the premises.

____Have the hood system professionally cleaned. Last cleaning was in 2000.
09/25/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.

____Test all smoke detectors in bedrooms and halls. Provide documentation upon reinspection.
09/25/2008 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 903.2.7 Group R. Existing sorority and fraternity house and existing Group R-4 occupancies shall have automatic sprinkler systems installed. A permit shall be issued within two years of the adoption of this code and the work shall be completed within three years of the adoption of this code.

____Sprinkler system required by October 22, 2010.