Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T08FR03117
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/25/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Extinguishers due for annual inspection/service. |
|
09/25/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. ____Commercial cooking extinguishig system due for inspection/service. |
|
09/25/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. ____Have the hood system professionally cleaned. Last cleaning was in 2000. |
|
09/25/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Test all smoke detectors in bedrooms and halls. Provide documentation upon reinspection. |
|
09/25/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 903.2.7 Group R. Existing sorority and fraternity house and existing Group R-4 occupancies shall have automatic sprinkler systems installed. A permit shall be issued within two years of the adoption of this code and the work shall be completed within three years of the adoption of this code. ____Sprinkler system required by October 22, 2010. |